BMM and BCM Class CC modular fuse blocksClass CC and supplemental modular ferrule fuse blocks
Description:
BCM (Class CC) and BMM (supplemental 13/32 x 1-1/2” /10x38) modular style fuse blocks with optional covers.
These Bussmann series fuse blocks contain multiple features to add versatility, reduce labor and enhance safety of any panel design.
Specifications
Ratings:
• Volts 600 Vac/dc
• Amps up to 30A
• SCCR up to 200kA (limited by fuse interrupting rating)
Agency information:
• Class CC BCM Series
• UL Listed File E14853, Guide IZLT
• CSA Certified 47235-6225-01
• CE
• RoHS Compliant
• 13/32” x 1-1/2” (Midget) BMM Series
• UL Recognized File E14853, Guide IZLT2
• CSA Certified 47235-6225-01
• CE
• RoHS Compliant
• Covers
• Covers are included in the overall UL Listing/ Recognition and CSA Certification
• IP20 finger-safe
• RoHS Compliant
Poles:
• 1-, 2-, 3-pole units factory assembled
• Single-pole units snap together to create desired number of poles
Flammability ratings:
• Blocks — UL 94V0, self-extinguishing
• Covers — UL 94HB, self-extinguishing
Features and benefits:
• Available in 1-, 2- and 3-pole configurations to meet stocking requirements.
• Blocks are fully modular with a snap-together design that provides tool-less assembly of multiple pole blocks at point-of-use to reduce inventory and save assembly time and labor.
• DIN-Rail and panel mount versatility allows one product to be used for multiple applications, lowering inventory cost.
• Compact footprint consumes minimal panel space.
• Optional see-through cover enhances safety with IP20 finger-safe protection, lockout/tagout capability and open circuit indication.
• Easy circuit identification with available universal marker labels for fuse block covers.
• Tin-plated bimetallic copper fuse clips deliver superior fatigue resistance compared to traditional spring brass.
• Terminal options to meet application needs including 1/4” spade quick connect terminals for faster panel assembly.
Operating and storage temperature range:
• Blocks -40°C to +120°C
• Non indicating covers -40°C to +120°C
• Indicating covers -20°C to +90°C*
* Indication requires minimum 90Vac/dc and closed circuit to illuminate.
Materials:
• Base — Thermoplastic
• Terminals — Tin-plated bimetallic copper
• Covers — Thermoplastic
• Screws and pressure plates — Zinc-plated steel
Cover catalog numbers:
• For blocks with quick connect terminals — CVR(I)-CCM-QC
• All other terminal options — CVR(I)-CCM
Recommended Bussmann series fuses:
• Class CC
• Ultimate protection time-delay Low-Peak LP-CC,data sheet No. 1023
• Advanced protection time-delay Limitron FNQ-R, data sheet No. 1014
• Advanced protection fast-acting Limitron KTK-R, data sheet No. 1015
• 13/32” x 1-1/2” (midget)
• Fast-acting 250Vac BAF, data sheet No. 2011
• Fast-acting 600Vac KTK, data sheet No. 1011
• Fast-acting 600Vac/dc KLM, data sheet No. 2020
• Time-delay 250Vac FNM, data sheet No. 2028
• Time-delay 500Vac FNQ, data sheet No. 1012
• 10x38mm (IEC)
• Class aM and gG/gL IEC industrial fuses, data sheet No. 720115
Recommended Bussmann series DIN-Rail end stops:
• Cat. no. BRKT-ND
• Cat. no. BRKT-NDSCREW2
Terminal for 75/90°C Cu and AL wire
Terminal type
AWG type/range
AWG
Torque lb-in (N•m)
Box lug (C)
CU 2-14 AL 2-8
CU 2-3
50 (5.6)
CU 4-6
45 (5.1)
CU 8-14
35 (4.0)
AL 2-6
50 (5.6)
AL 8
40 (4.5)
Screw (S)
CU 10-18
10-18
20 (2.3)
Screw/quick connect* (SQ)
Pressure plate (P)
Pressure plate/ quick connect* (PQ)
* ¼“ Quick Connect terminal maximum ampacity dependent on female spade connector and wire ratings
Terminal type
#10-32 Phil-slot screw
Screw with quick connect*
Pressure plate
Pressure plate with quick connect*
Box lug
Poles
Fuse class
BCM603-1S
BCM603-1SQ
BCM603-1P
BCM603-1PQ
BCM603-1C
1
CC
BCM603-2S
BCM603-2SQ
BCM603-2P
BCM603-2PQ
BCM603-2C
2
CC
BCM603-3S
BCM603-3SQ
BCM603-3P
BCM603-3PQ
BCM603-3C
3
CC
BMM603-1S
BMM603-1SQ
—
BMM603-1PQ
BMM603-1C
1
10x38 (13/32”x1-1/2”)
BMM603-2S
BMM603-2SQ
—
BMM603-2PQ
BMM603-2C
2
10x38 (13/32”x1-1/2”)
BMM603-3S
BMM603-3SQ
—
BMM603-3PQ
BMM603-3C
3
10x38 (13/32”x1-1/2”)
—
BCCMM603-3SQ
—
BCCMM603-3PQ
—
3
3-Pole control circuit transformer block 2-pole CC with 1-pole 10x38 (13/32”x1-½”)
* ¼“ Quick Connect terminal maximum ampacity dependent on female spade connector and wire ratings
Table 2. Recommended covers*
Terminal type
Cover catalog numbers
Indicating
Non indicating
Box lug (C)
CVRI-CCM
CVR-CCM
Screw (S)
CVRI-CCM
CVR-CCM
Screw/quick connect* (SQ)
CVRI-CCM-QC
CVR-CCM-QC
Pressure plate (P)
CVRI-CCM
CVR-CCM
Pressure plate/ quick connect* (PQ)
CVRI-CCM-QC
CVR-CCM
* For use with 4AWG max conductors.
Features and benefits:
• Modular, snap-together design provides tool-less assembly of multiple poles to save inventory and reduce assembly time.
• DIN-Rail and panel mount versatility allows products to be used for multiple applications and lowers inventory cost.
• Optional see-through covers enhance safety with IP20 finger-safe protection, lockout/ tagout capability and optional open circuit indication.
• Fuse block covers feature easy circuit identification with available universal marker labels.
• Patented design of Class CC blocks provides up to 30% less heat rise and 40% less watts loss than competitive products.
-