Square Body DIN 43 620 — 690V (IEC): 10-800A Class gR — Full Range Fuses
Specifications
Description: Square body DIN 43 620 blade style high speed fuses.
Dimensions: See dimensions illustration.
Ratings:
Volts: — 690Vac (IEC)
Amps: — 10-800A IR: — 300kA RMS Sym.
Agency Information: CE, Designed and tested to IEC 60269: Part 4, UL Recognized.
Electrical
Characteristics
Total clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage Eg , (rms) at a power factor of 15%
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Catalog Numbers
Catalog Numbers
Electrical Characteristics
Type T Indicator For Micro
Size
Amp
Vac
170M2691
00
10
690
170M2692
16
170M2693
20
170M2694
25
170M2695
32
170M2696
40
170M2697
50
170M2698
63
170M2699
80
170M2700
100
170M2701
125
170M2702
160
170M4176
1
50
170M4177
63
170M4178
80
170M4179
100
170M4180
125
170M4181
160
170M4182
200
170M4183
250
170M4184
315
170M4185
350
170M4186
400
170M5881
2
200
170M5882
250
170M5883
315
170M5884
350
170M5885
400
170M5886
450
170M5887
500
170M5888
550
170M5889
630
170M6080
3
350
170M6081
400
170M6082
450
170M6083
500
170M6084
550
170M6085
630
170M6086
700
170M6087
800
*The RMS amp rating of this fuse range is given with open fuse bases connected to copper conductors according to IEC 60269, Part 1, table 10. When used in enclosed fuse bases/ disconnects, derating factors have to be observed.
Please contact Cooper Bussmann for application assistance.
• Watts loss provided at rated current.
• Microswitch ordered separately. See accessories on page 185-186.
• For fuse curves see pages 142 and 143.
Features and Benefits
• Excellent DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss
• Superior cycling capability
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
For Operating Class aR Fuses in This Body Style
• See page 132
-