Fusetron™ 600V Class RK5 FRS-R — 600 Vac/300 Vdc, 1/10-60 A, dual element, time-delay fuses
-
Fusetron™ 600V Class RK5 FRS-R — 600 Vac/300 Vdc, 65-600 A, dual element, time-delay fuses
Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/300 Vdc, 1/10-60 A, dual element, time-delay fuses
Catalog symbol:
-
FRS-R-(amp) (non-indicating)
-
FRS-R-(amp)ID (indicating)
Description:
Advanced protection, energy efficient Class RK5 dual-element, current-limiting, time-delay fuses with optional open fuse indication on select ratings. Time-delay — 10 second (minimum) at 500% of rated current.
Specifications:
Ratings
Volts :
-
600 Vac, 300 Vdc (1/10-30 A)
-
600 Vac, 250 Vdc* (35-60 A)
Amps :1/10 -600A
Interrupting rating
-
200 kA Vac RMS Sym
-
20 kA Vdc
Agency information
-
UL® Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
-
CSA® Certified, C22.2 No. 248.12, Class 1422-02, File 53787
-
CE
Catalog Numbers (Amps)
Catalog Numbers
Catalog Numbers
Catalog Numbers
Catalog Numbers
FRS-R-1/10
FRS-R-1-1/4
FRS-R-4
FRS-R-15
FRS-R-1/8
FRS-R-1-4/10
FRS-R-4-1/2
FRS-R-17-1/2
FRS-R-15/100
FRS-R-1-1/2
FRS-R-5
FRS-R-20
FRS-R-2/10
FRS-R-1-6/10
FRS-R-5-6/10
FRS-R-25
FRS-R-1/4
FRS-R-1-8/10
FRS-R-6
FRS-R-30
FRS-R-3/10
FRS-R-2
FRS-R-6-1/4
FRS-R-35
FRS-R-4/10
FRS-R-2-1/4
FRS-R-7
FRS-R-40
FRS-R-1/2
FRS-R-2-1/2
FRS-R-7-1/2
FRS-R-45
FRS-R-6/10
FRS-R-2-8/10
FRS-R-8
FRS-R-50
FRS-R-8/10
FRS-R-3
FRS-R-9
FRS-R-60
FRS-R-1
FRS-R-3-2/10
FRS-R-10
FRS-R-1-1/8
FRS-R-3-1/2
FRS-R-12
* Open fuse indication available by inserting the suffix “ID.” E.g., FRS-R-15ID. 35 to 60 amp indicating fuses are not Vdc rated.
Carton Quantity
Amp Rating
Carton Qty.
1-60
10
Features and benefits
-
Dual-element feature provides the best time-delay performance, allowing closer sizing and superior protection of motors and transformers
-
Closer sizing allows for smaller fuses and less costly switches
-
Class RK5 fuses with a 200 kA interrupting rating for use in a broad range of applications
-
Provides motor overload, ground fault, and short-circuit protection
-
Helps protect motors against burnout from overloads and single-phasing when sized properly
-
Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short-circuit and overload protection
-
Offers a 10-second time delay at 5 times the rated current
-
The time-delay feature makes it possible to use fuse amp ratings that are much smaller than those of non-time delay fuses. Considerable cost savings occur by permitting the use of smaller size switches, panels, and fuses themselves.
-
Provides current limitation to help protect downstream components from high fault currents.
-
Gives motor running back-up protection to motors without extra costs.
Recommended fuse blocks
Amps
Catalog no
1-Pole
2-Pole
3-Pole
30
RM60030-1_
RM60030-2_
RM60030-3_
60
RM60060-1_
RM60060-2_
RM60060-3_
For additional information on the 600 volt fuse blocks, see data sheet no. 10489. For additional information on the RM600 volt fuse blocks, see data sheet No. 10489
Fuse reducers for Class R fuses
Equipment fuse clips
Desired fuse (case)
Catalog no. (pairs)
size
600 V
60A
30A
NO.663-R
100A
30A
NO.246-R
60A
NO.616-R
200A
60A
NO.626-R
Current-limiting effects
Prosp. S.C.C.
Let-through current
(apparent RMS symmetrical vs. fuse rating)
-
30A
60A
5000
1000
1000
10000
1000
2000
15000
1000
2000
20000
2000
2000
25000
2000
2000
30000
2000
3000
35000
2000
3000
40000
2000
3000
50000
2000
3000
60000
2000
3000
70000
3000
4000
80000
3000
4000
90000
3000
4000
100000
3000
4000
150000
3000
5000
200000
4000
6000
Fusetron™ 600V Class RK5 FRS-R — 600 Vac/300 Vdc, 65-600 A, dual element, time-delay fuses
Catalog symbol: FRS-R-(amp)
Description:
Advanced protection, energy efficient Class RK5 dual element, current-limiting, time-delay fuses. Time-delay – 10 seconds (minimum) at 500% of rated current.
Specifications:
Ratings
Volts : 600Vac, 300Vdc
Amps : 65-600A
Interrupting rating
-
200 kA Vac RMS Sym
-
20 kA Vdc
Agency information :
-
UL® Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
-
CSA® Certified, C22.2 No. 248.12, Class 1422-02, File 53787
-
CE
Catalog numbers (amps) :
Catalog Numbers
Catalog Numbers
Catalog Numbers
Catalog Numbers
FRS-R-65
FRS-R-100
FRS-R-200
FRS-R-400
FRS-R-70
FRS-R-110
FRS-R-225
FRS-R-450
FRS-R-75
FRS-R-125
FRS-R-250
FRS-R-500
FRS-R-80
FRS-R-150
FRS-R-300
FRS-R-600
FRS-R-90
FRS-R-175
FRS-R-350
Carton quantity :
Amp Rating
Carton Qty.
65-100
1
101-200
1
201-400
1
401-600
1
Features:
-
Provides motor overload, ground fault and short-circuit protection. When used in circuits subject to surge currents such as those caused by motors, transformers and other inductive components, these fuses can be sized close to full-load amps to give maximum overcurrent protection
-
The time-delay feature makes it possible to use fuse amp ratings which are much smaller than those of non-time delay fuses. Considerable cost saving occurs by permitting the use of smaller size switches, panels and fuses themselves
-
Provides a good degree of short-circuit protection (greater current-limitation) to help protect downstream components from high fault currents
-
Gives motor running back-up protection to motors without extra cost
-
Helps protect motors against burnout from overloads and single-phasing when sized properly
-
Simplifies and improves blackout prevention (selective coordination ratios)
-
Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high-performance, short-circuit and overload protection
Dimensions - in:
Amp ratings
A
B
65-100
7.88
1.11
1110-200
9.63
1.61
225-400
11.63
2.34
450-600
13.38
2.88
Recommended fuse blocks :
Fuse amps
1-Pole
2-Pole
3-Pole
70-100
RM60100-1CR
RM60100-2CR
RM60100-3CR
110-200
RM60200-1CR
RM60200-2CR
RM60200-3CR
225-400
RM60400-1CR
RM60400-2CR
RM60400-3CR
450-600
RM60600-1CR
RM60600-2CR
RM60100-3CR
Fuse reducers for class R fuses :
Equipment fuse clips
Desired fuse (case) size
Catalog numbers (pairs) 600 V
200A
100A
NO.2621-R
400A
100A
NO.2641-R
200A
NO.642-R
100A
NO.2661-R
600A
200A
NO.2662-R
400A
NO.2664-R+
† Single reducer only (pair not required).
For additional information on Class R fuse reducers, see data sheet No. 1118.
Current-limiting effects :
Prospective S.C.C.
Let-through current
(apparent RMS symmetrical vs. fuse rating)
100A
200A
400A
600A
5000
3000
4000
5000
5000
10000
4000
5000
9000
10000
15000
4000
60000
10000
14000
20000
5000
7000
11000
15000
25000
5000
7000
12000
17000
30000
5000
8000
13000
18000
35000
5000
8000
13000
18000
40000
6000
9000
14000
19000
50000
6000
9000
14000
20000
60000
6000
10000
15000
22000
70000
7000
11000
17000
23000
80000
7000
12000
17000
23000
90000
7000
12000
17000
24000
100000
8000
13000
18000
25000
150000
9000
14000
21000
27000
200000
9000
16000
23000
32000
-
-