Ferrule — FWP 22 x 58mm 690V/700V (IEC/UL): 20-100A, Striker Optional
New - gR operating class with and without striker
Eaton’s Bussmann series FWP 14x51 mm class gR fuses provide full range overload and short-circuit protection and are used to protect AC/DC drives and semi conductors.
They are available with an optional striker to provide local indication of fuse status or work in the CH22 modular fuse holder to provide remote fuse indication capabililty.
aR operating class with and without striker
Eaton’s Bussmann series FWP 22x58 mm class aR fuses provide short-circuit protection and are used to protect AC/DC drives and semi conductors.
They are available with an optional striker to provide local indication of fuse status or work in the CH22 modular fuse holder to provide remote fuse indication capabililty.
Description:
Ferrule style high speed fuses. with and without indicating striker.Ratings:
Volts: 690Vac (IEC); 700Vac (UL)
Amps: 20-100A
IR: 200kA RMS Sym. 50kA @ 500VdcAgency Information: CE, UL Recognition
Features and Benefits
• Excellent cycling capability and dc performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss in a compact size
• Used with finger-safe holders/blocksTypical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage startersCatalog Numbers
Fuse type
Fuse symbol
Rated voltage
Rated current (amps)
12t (A2s)
Watts loss (w)*
Catalog no
Pre-arcing
Clearing at 600 Vac
without striker
22*58mm (7/8*2-9/32)
700 Vac/dc (UL)
20
23
390
5
FWP-20A22F
25
37
630
6
FWP-25A22F
32
55
780
8
FWP-32A22F
40
88
960
12
FWP-40A22F
50
155
2200
12.5
FWP-50A22F
63
280
4000
15
FWP-63A22F
80
550
7800
15
FWP-80A22F
100
1100
15600
16.5
FWP-100A22F
with striker
22*58mm (7/8*2-9/32)
700 Vac/dc (UL)
20
19
260
6
FWP-20A22FI
25
34
410
6
FWP-25A22FI
32
53.5
605
8
FWP-32A22FI
40
68
760
9
FWP-40A22FI
50
135
1600
9.5
FWP-50A22FI
63
280
3080
11
FWP-63A22FI
80
600
6600
13.5
FWP-80A22FI
100
1100
12500
16
FWP-100A22FI
Without Striker Catalog Numbers (Amps)
Catalog Numbers
Catalog Numbers
Catalog Numbers
Catalog Numbers
FWP-20A22F
FWP-32A22F
FWP-50A22F
FWP-80A22F
FWP-25A22F
FWP-40A22F
FWP-63A22F
FWP-100A22F
With Striker Catalog Numbers (Amps)
Catalog Numbers
Catalog Numbers
Catalog Numbers
Catalog Numbers
FWP-20A22FI
FWP-32A22FI
FWP-50A22FI
FWP-80A22FI
FWP-25A22FI
FWP-40A22FI
FWP-63A22FI
FWP-100A22FI
Electrical Characteristics
Total Clearing I2t The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms).
Arc Voltage
This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Power Losses
Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Carton Quantity
Amp Rating
Carton Qty
20-100
10
*IEC/UL Voltage rating 690/700
-