FWP 14x51 mm Class aR fuses
Specifications:Eaton’s Bussmann series FWP 14x51 mm class aR fuses provide short-circuit protection and are used to protect AC/DC drives and semi conductors
They are available with an optional striker to provide local indication of fuse status or work in the CH14 modular fuse holder to provide remote fuse indication capabililty.
Description: Ferrule style high speed fuses with and without indicating striker. Dimensions: See dimensions illustrations.
Ratings:
Volts: 690Vac (IEC) — 700Vac (UL) — 800Vdc (5-50A)
Amps: 1-50A
IR: 200kA RMS Sym. — 50kA @800Vdc
Agency Information: CE, UL Recognition, CSA
Component Acceptance for versions without indicator only.
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and at power factor of 15% are given in the electrical characteristics. For other voltages, the clearing I2t is found by multiplying by correction factor, K, given as a function of applied working voltage, Eg, (rms)
Arc Voltage This curve gives the peak arc voltage, UL, which may appear across the fuse during its operation as a function of the applied working voltage, Eg, (rms) at a power factor of 15%.
Power Losses Watts loss at rated current is given in the electrical characteristics. The curve allows the calculation of the power losses at load currents lower than the rated current. The correction factor, Kp, is given as a function of the RMS load current, Ib, in % of the rated current.
Without Striker Catalog Numbers (Amps)
Catalog Numbers
Catalog Numbers
Catalog Numbers
Catalog Numbers
FWP-1A14Fa
FWP-5A14Fa
FWP-20A14Fa
FWP-40A14Fa
FWP-2A14Fa
FWP-6A14Fa
FWP-25A14Fa
FWP-50A14Fa
FWP-3A14Fa
FWP-10A14Fa
FWP-30A14Fa
FWP-4A14Fa
FWP-15A14Fa
FWP-32A14Fa
With Striker Catalog Numbers (Amps)
Catalog Numbers
Catalog Numbers
Catalog Numbers
Catalog Numbers
FWP-10A14FI
FWP-20A14FI
FWP-30A14FI
FWP-40A14FI
FWP-15A14FI
FWP-25A14FI
FWP-32A14FI
FWP-50A14FI
• Watts loss provided at rated current.
• See accessories on page 216.
Fuse type
Fuse symbol
Rated voltage
Rated current (amps)
12t (A2s)
Watts loss (w)*
Catalog no
Pre-arcing
Clearing at 600 Vac
without striker
14*51mm (9/16*2)
700Vac (UL)
1
0.04
0.41
6.7
FWP-1A14Fa
2
0.08
0.11
8.7
FWP-2A14Fa
3
0.11
0.26
2.8
FWP-3A14Fa
4
0.1
0.23
3
FWP-4A14Fa
600Vac (IEC)700 Vac/dc (UL)
5
2
11
1.6
FWP-5A14Fa
10
4
22
4
FWP-10A14Fa
15
10
70
5.5
FWP-15A14Fa
20
26
180
6.6
FWP-20A14Fa
25
49
320
7
FWP-25A14Fa
30
58
400
9
FWP-30A14Fa
32
68
600
8
FWP-32A14Fa
40
84
750
8
FWP-40A14Fa
50
200
1800
9
FWP-50A14Fa
with striker
14*51mm (9/16*2)
700 Vac/600 Vdc (UL)
10
4
32
2
FWP-10A14FI
15
7
63
4
FWP-15A14FI
20
26
234
4
FWP-20A14FI
25
42
378
4
FWP-25A14FI
30
52
468
6
FWP-30A14FI
32
68
600
8
FWP-32A14FI
40
84
750
8
FWP-40A14FI
50
200
1800
9
FWP-50A14FI
Carton Quantity
Amp Rating
Carton Qty
1-60
10
Features and Benefits
• Excellent cycling capability and DC performance
• Low arc voltage and low energy let-through (I2t)
• Low watts loss in a compact size
• Used with finger-safe holders/blocks
-